Rockwell Disclaimer: The product is used surplus. This website is not sanctioned or approved by any manufacturer or tradename listed. Designated trademarks, brand names and brands appearing herein are the property of their respective owners. Products sold by come with ’s 1-year, 2-year, or 3-year warranty and do not come with the original manufacturer’s warranty. is not an authorized distributor, affiliate, or representative for the brands we carry. Appreciate you could feedback on your process after trying this method. Under the RSLins Enterprise driver add the RSLogix Emulate 5000 virtual PLC as your project device shortcut. You need to key in the IP address for the PC where you run the RSLogix Emulate 5000 4. Under the Communication Setup, right click on the Ethernet and add the device driver for RSLinx Enterprise (Check your revision, most properly will be Major Revision 2). Open your targeted PanelView Plus project's in FTView Studio. Under the Ethernet properties tick the Listen on Ethernet/IP encapsulation ports and your RSLinx Enterprise's Ethernet communication port will be available through your PC's physical Ethernet port. Open any project and under the Communication Setup, right click on the Ethernet and select properties. You must not delete the RSLinx Enterprise slot from the Emulator you must left the it running as shown in the following picture. Here is the proper way if you want to connect your PanelView Plus to RSLogix Emulate 5000 via Ethernet: 1.